Requirements of the AS and IEC Standards
The neutral conductor is connected to the neutral point of a system and is intended to carry current under normal conditions. The neutral conductor is required for each main circuit and there are rules in the Standards for its sizing.
This article summarises the requirements of Standards AS/NZS 3000 and IEC 60364-5-52.
Neutral Sizing according to Standard AS/NZS 3000
The neutral conductor of circuits designed to Australian and New Zealand Standard AS/NZS 3000 must have the same current-carrying capacity (same size) as the associated active conductors.
When there are substantial harmonics then the neutral conductor size may need to be larger than the active conductors or in the case of a multi-core cable the neutral currents may dictate the size of the active.
An exception is for multi-phase circuits feeding predominantly multi-phase loads (balanced phases). In this case the neutral conductor size may be smaller than the active conductor size but must be sized to carry at least the out-of-phase current.
Type of Circuit | Neutral conductor size requirement | |
---|---|---|
Single phase two-wire
| Neutral conductor size not less than active conductor size. | Sneutral = Sactive |
Multiphase
| Neutral conductor may be required to be larger than associated active conductors. Refer to IEC 60364-5-52. | Sneutral ≥ Sactive |
Multiphase
| Neutral conductor must be capable of carrying the maximum out-of-balance current, including any harmonic component. | Sneutral ≤ Sactive |
Neutral Sizing according to Standard IEC 60364-5-52
For multiphase circuits:
The neutral conductor size can be smaller than the active size if harmonic current is < 15 %.
When harmonics are between 15 % to 33 % the neutral conductor size shall be the same size as the active conductor.
For multicore cables when harmonics are above 33 % the neutral conductor size and the active conductor size must carry 1.45 times the load current.
For single core cables when harmonics are above 33 % the neutral conductor size must be sufficient to carry 1.45 times the load current and can be larger in size than the active conductors.
Type of Circuit | Neutral conductor size requirement | |
---|---|---|
Single phase two-wire
| Neutral conductor size same as the active conductor size. | Sneutral = Sactive |
Multiphase
| Neutral conductor must be capable of carrying the maximum out-of-balance current, including any harmonic component. | Sneutral ≤ Sactive |
Multiphase
| Neutral conductor size same as the active conductor size. | Sneutral = Sactive |
Multiphase - multicore cable
| Neutral conductor must be sized to carry at least 1.45 times the active load current | Sneutral = Sactive Both sized to carry 1.45 x IB |
Multiphase - single core cable
| Neutral sized to carry at least 1.45 times the load current | Sneutral > Sactive Both sized to carry 1.45 x IB |
Cable Pro Web
Cable sizing and maximum demand software in the cloud. No installation, use on any device.
Try For Free
Related Articles:
May 29, 2019
5 mins read
Understanding Earth Fault Loop Impedance
The purpose of this document is to provide a better understanding of Fault Loop Impedance, also referred to as Earth Fault Loop Impedance so that the requirements of AS/NZS 3000 Wiring Rules for safety, design, installation and testing of electrical installation may be met.
ELEK Software
729
- Low Voltage Design
April 6, 2019
1 min read
Voltage drop limits for Low Voltage installations
Voltage Drop Limits per the Wiring Rules AS/NZS 3000 as well as rules of thumb to assist with electrical design. Includes AC and DC voltage drop or rise limits.
ELEK Software
488
- Low Voltage Design
November 28, 2018
5 mins read
Cable Current Rating Derating Factors Explained
Derating factors are applied to the cable current rating ensuring that cable operating temperature limits are not exceeded. Derating factors are derived to match the specific cable installation conditions.
ELEK Software
655
- Low Voltage Design
July 3, 2018
5 mins read
Maximum Demand Tables
Reference tables for diversity factors and energy demand from Wiring Rules AS/NZ 3000 for domestic and non-domestic installations.
ELEK Software
521
- Low Voltage Design
June 24, 2020
5 mins read
Cable Pulling Tension Calculations
This article explains how to perform cable pulling tension and sidewall pressure calculations and also includes an example.
ELEK Software
514
- Low Voltage Design
May 16, 2020
4 mins read
Automatic Maximum Demand Calculations
The new maximum demand module provides fast and accurate calculations for loads in accordance with rules from the Standards and for custom loads. An ingenious automatic phase balancing algorithm ensures maximum demand and phase imbalance are both minimised.
ELEK Software
397
- Low Voltage Design
April 2, 2020
6 mins read
Voltage Rise Calculations
Voltage rise can occur in solar PV systems on the AC side between the power inverters and network connection point. Voltage rise calculations are no different to those for voltage drop.
ELEK Software
401
- Low Voltage Design
July 3, 2018
1 min read
Maximum Demand
The 4 main approaches for determining the maximum demand of an electrical installation are discussed.
ELEK Software
389
- Low Voltage Design
February 13, 2020
0 mins read
Accurate voltage drop calculations
Accurately calculating voltage drop results in lower voltage drops which leads to smaller cable sizes and saves money.
ELEK Software
286
- Low Voltage Design
Print this article:
Cable Pro Web
Cable sizing, maximum demand and protection design software.
Try For Free
Watch Demo Video
As used by: